Features
Adoption of a hybrid VCB*1
- The number of parts in the operation mechanism has been reduced by 85% compared to our former models, and solid lubrication has been adopted for all sliding parts to achieve greaseless operation, resulting in improved reliability and safety.
- Maintainability has been improved by reduction of the number of parts and greaseless design, achieving reduced LCC*2.
- Hybrid-type VCB: A vacuum circuit breaker incorporating permanent magnets, electromagnets, and a spring-operated mechanism.
- LCC (life-cycle cost): The whole-life cost of a product, which is the initial cost plus the running cost.
Safety
- Safety is ensured by housing the main circuit equipment, including busbars, in a solid, earthed metal container.
- Insulation is provided by nonflammable SF6 gas.
- The insulation performance has been confirmed to withstand the system voltage even if the gas pressure drops to atmospheric pressure.
Maintainability
- Adoption of a hybrid VCB has reduced inspection work and extended inspection cycles.
Environmental performance
- Optimized storage equipment layout design and low gas pressure reduce SF6 gas consumption by 14% compared to former models, contributing to the realization of a sustainable society.
Specification
| Item | Rated specifications | ||
|---|---|---|---|
| Rated voltage | 72kV | 84kV | |
| Lightning impulse withstand voltage | 350kV | 400kV | |
| Power-frequency withstand voltage | 140kVrms | 160kVrms | |
| Rated current | 800A/1,200A | ||
| Rated frequency | 50Hz/60Hz | ||
| Rated breaking current | 25kA | ||
| Rated making current | 62.5kA | ||
| Rated short-time withstand current | 25kA(2s) | ||
|
SF6 rated gas pressure (Minimum guaranteed gas pressure) (at 20°C) |
GIS compartment | 0.07MPa G (0.05MPa G) | |
| VCT compartment | 0.16MPa G (0.13MPa G) | ||
| Compliant standards |
JEC-2350 (2016) JEM 1499 (2012) |
||
| EDS opening/closing performance | Leading small current switching | 84kV、0.1Ax200回 | Lagging small current switching | 84kV、3Ax100回 |