Power Distribution and TransmissionLogger Touch Panel DE-HSLTP
Easy system construction without the need for a PC.
Can be set up with the touch panel alone without the need for programming

Features
System construction without the need for network or PC connection
The logger touch panel unit stores various measurement data on a USB
flash drive, eliminating the need to install a monitoring PC and
allowing monitoring and data storage for all connected devices in the
cubicle.
In addition, setting the CO2 emission coefficient allows
easy visualization of the CO2 emissions from the electricity usage by
the power receiving equipment.
Easy and secure setup and operation
The recorded data can be displayed and saved, and each monitoring unit
can be easily configured with the touch panel.
In the standard
configuration, measurement data is stored in a USB flash drive, which
eliminates the need to install communication lines, and no network is
used, enabling secure operation.
Integration with a host system
Modbus TCP communication*1 is supported, enabling data acquisition from a host system, CSV data acquisition via an FTP server*2, and remote monitoring by using optional software.
- Modbus TCP communication: Network standard announced by Schneider (France)
System configuration

Connectable units
| Model | Type |
|---|---|
| Meter/panel-mounted power monitoring unit | DE-HSF* DE-HSB* |
| Electrical energy calculation unit | DE-8WH4B*R DE-4WH2B*R |
| Electrical energy calculation unit (3-phase 4-wire) | DE-34WHB* |
| Pulse input unit | DE-16PB3 DE-8PB3 |
| Analog input unit | DE-4ARB |
| Insulation monitoring unit | ZE-*** |
| Transformer and equipment monitoring unit | DE-TREQ* |
Specification
| Item | Specification | |
|---|---|---|
| Screen | Current value |
Shows the current value of each unit. The color of the display changes for warnings. |
| Trend graph |
Gives a graphical display of data measured every 10 minutes. Data for the past 30 days can be displayed. |
|
| Demand monitoring |
Shows the demand status calculated by the transformer/equipment
monitoring unit. Demand monitoring is not available with other units. |
|
| Warning information | Shows warning from status monitoring. | |
| Setting | Used for configuring various settings. | |
| Functions | Data storage | Stores measurement data every 10 minutes to USB flash drive in the CSV format. |
| Status monitoring |
Monitors the following statuses. Contact change of pulse input unit, caution/alert level overrun of insulation monitoring unit, analog input unit upper and lower limit monitoring, and leakage current, temperature, analog, contact, and demand monitoring for transformer and equipment monitoring units. |
|
| Remote monitoring | The optional software EX-Viewer can be used to display and operate the same screen as the touch panel screen. | |
| FTP data retrieval | CSV data in the USB flash drive can be retrieved via FTP. | |
| Modbus TCP communication | The current values of H-NET units connected to this product can be acquired from a host system via communication. | |
| Touch panel | Manufacturer | Schneider Electric Holdings, Inc. |
| Brand | Pro-Face | |
| Manufacturer’s type | PFXST6400WADE | |
| Display size | 7” (wide) | |
| Serial communication | Protocol | Modbus RTU (communication speed 19.2 kbps, no parity) |
| Host communication | Interface | Ethernet |
| Functions | Remote monitoring (TCP/UDP), file transfer (FTP), measurement value acquisition (Modbus TCP) | |
| Power supply | Rated voltage | DC24V |